KEYENCE KV-E4XT PLC
Model |
KV-E4XT |
|||
Number of inputs |
4 |
|||
Minimum ON voltage |
19V |
|||
Maximum OFF current |
2mA |
|||
Input time constant (switchable between 2 levels by using special auxiliary relays 2609 to 2612) |
10 ms ± 20%, 10 µs ± 20% for both rising (OFF to ON) and falling (ON to OFF) edges |
|||
Number of outputs |
4 |
|||
Output |
Transistor (NPN)*1 |
|||
Rated load voltage |
30 VDC |
|||
Rated output current |
0.5 A/output |
|||
Leakage current (at OFF) |
100 µA or less |
|||
Residual voltage (at ON) |
0.8 V or less |
|||
Startup operation time (OFF → ON) |
50 µs or less |
|||
Startup operation time (ON → OFF) |
250 µs or less |
(2E-07, Box 6)